VHR
NHR load series products——AC load
Release time:2017-02-23 14:25:52 | viewed:

The 4600 series AC electronic load is designed for UPS, inverter and other AC output of power supply products testing. Adjustable crest factor and power factor to make the load can be configured to linear load or nonlinear load to meet the customer's products in different conditions of the test requirements, and is more flexible and reliable than various of resistive load.


         


Ø High precision measurement:

Through the internal circuit, the 4600 series electronic load can realize the high precision measurement of frequency, voltage, peak voltage, current, current peak, peak coefficient, power factor, apparent power, active power, reactive power, peak power, resistance, this kind of measurement capability can avoid the needed external measuring instrument or equipment, reduce cost and improve test speed.


Ø The extensive application fields:

In order to meet the needs of majority of UPS, inverter and other AC output products test, the 4600 series ac load is divided into two sub-series: 3KW series (4600-3) and 6KW series (4600-6), you can parallel many sets of load to meet the needs of more power. Besides, the load can be operated in the CC, CV, CR, CP, SC, UPF, CNL modes.


Ø PC software——empower:

Through the PC software emPower, the 4600 series electronic load can be monitored and controlled, besides, you still can complete real-time waveform display function via this software.


 


4600

4600-3

4600-6

4600-12

4600-18

4600-24

4600-36

Power

3kW

6kW

12kW

18kW

24kW

36kW

Maximum Current

30A

60A

120A

180A

240A

360A

Voltage Range

50-350V

50-350V

50-350V

50-350V

50-350V

50-350V

Programmable Modes


Constant Current







Range (RMS)

0-30A

0-60A

0-120A

0-180A

0-240A

0-360A

Accuracy

0.20%

0.20%

0.20%

0.20%

0.20%

0.20%

Resolution

0.05%

0.05%

0.05%

0.05%

0.05%

0.05%

Constant Voltage







Range

50-350V

50-350V

50-350V

50-350V

50-350V

50-350V

Accuracy

0.20%

0.20%

0.20%

0.20%

0.20%

0.20%

Resolution

0.05%

0.05%

0.05%

0.05%

0.05%

0.05%

Constant Power







Range

300W-3kW

600W-6kW

1.2-12kW

1.8-18kW

2.4-24kW

3.6-36kW

Accuracy

0.50%

0.50%

0.50%

0.50%

0.50%

0.50%

Resolution

0.05%

0.05%

0.05%

0.05%

0.05%

0.05%

Constant Resistance







Range

2.5-100,100-1000Ω

1.25-50,50-500Ω

0.63-25,25-250Ω

0.42-17,17-167Ω

0.31-12.5,12.5-125Ω

0.2-8.3,8.3-83Ω

Accuracy

1.50%

1.50%

1.50%

1.50%

1.50%

1.50%

Resolution

0.05%

0.05%

0.05%

0.05%

0.05%

0.05%

Short Circuit







Max Surge Current

300A

600A

1200A

1800A

2400A

3600A

Power Factor







Range

0-1, lead/lag

0-1, lead/lag

0-1, lead/lag

0-1, lead/lag

0-1, lead/lag

0-1, lead/lag

Accuracy

1%

1%

1%

1%

1%

1%

Resolution

0.05

0.05

0.05

0.05

0.05

0.05

Crest Factor







Range

1.414-4

90 A limit

1.414-4

180 A limit

1.414-4

360 A limit

1.414-4

540 A limit

1.414-4

720 A limit

1.414-4

1080 A limit

Accuracy

1%

1%

1%

1%

1%

1%

Resolution

0.05%

0.05%

0.05%

0.05%

0.05%

0.05%

Macros

Queues of up to 100 commands can be run manually or from a triggered event such as phase angle, input voltage level, or system trigger

Custom Waveforms

User-defined waveforms can be created through a full-screen graphical editor that provides control of current, voltage, resistance, power, crest factor and power factor

Measurements


Current







Ranges (RMS)

0-30A

0-60A

0-120A

0-180A

0-240A

0-360A

Accuracy

0.20%

0.20%

0.20%

0.20%

0.20%

0.20%

Peak Current







Ranges

0-90A

0-180A

0-360A

0-540A

0-720A

0-1080A

Accuracy

0.50%

0.50%

0.50%

0.50%

0.50%

0.50%

Voltage







Ranges

50-350V

50-350V

50-350V

50-350V

50-350V

50-350V

Accuracy

0.10%

0.10%

0.10%

0.10%

0.10%

0.10%

Peak Voltage







Ranges

50-500V

50-500V

50-500V

50-500V

50-500V

50-500V

Accuracy

0.50%

0.50%

0.50%

0.50%

0.50%

0.50%

Frequency







Ranges

45-440Hz

45-440Hz

45-440Hz

45-440Hz

45-440Hz

45-440Hz

Accuracy

0.10%

0.10%

0.10%

0.10%

0.10%

0.10%

True Power







Ranges

0-10.5kVA

0-21kVA

0-42kVA

0-63kVA

0-84kVA

0-126kVA

Accuracy

0.20%

0.50%

0.50%

0.50%

0.50%

0.50%

Apparent Power







Ranges

0-10.5kVA

0-21kVA

0-42kVA

0-63kVA

0-84kVA

0-126kVA

Accuracy

0.30%

0.30%

0.30%

0.30%

0.30%

0.30%

Reactive Power







Ranges

0-10.5kVA

0-21kVA

0-42kVA

0-63kVA

0-84kVA

0-126kVA

Accuracy

0.30%

0.30%

0.30%

0.30%

0.30%

0.30%

Peak Power







Ranges

0-45kW

0-90kW

0-180kW

0-270kW

0-360kW

0-540kW

Accuracy

1.00%

1.00%

1.00%

1.00%

1.00%

1.00%

Resistance







Ranges

2.5-100,100-1000Ω

1.25-50,50-500Ω

0.63-25,25-250Ω

0.42-17,17-167Ω

0.31-12.5,12.5-125Ω

0.2-8.3,8.3-83Ω

Accuracy

1%,5%

1%,5%

1%,5%

1%,5%

1%,5%

1%,5%

Crest Factor







Ranges

1.414-4

1.414-4

1.414-4

1.414-4

1.414-4

1.414-4

Accuracy

0.50%

0.50%

0.50%

0.50%

0.50%

0.50%

Power Factor







Ranges

0-1 lead/lag

0-1 lead/lag

0-1 lead/lag

0-1 lead/lag

0-1 lead/lag

0-1 lead/lag

Accuracy

0.50%

0.50%

0.50%

0.50%

0.50%

0.50%

Waveform Display

Continuously updated, graphical display of a full cycle of current, voltage and/or power waveforms

Additional Features


3-Phase Operation

Provides for control of 3 Operation individual units (for example,3kVA units for a total of 9kVA,6kVA units for a total of18 kVA) to simulate a 3-phase load

Self Test

Power-up self test of all major functions including status of input, output, control and protection circuits

Protection

OP, OC, OV, OT, and Under voltage Lockout

Operating Temperatue

0-50℃

 

 